Conception, manufacturing and installation of generating sets and power plants, welding sets, water pumps, lighting towers.

V250U - Generating set

VOLVO, TAD734GE
LEROY SOMER LSA462L9-SH-F12


V250U Power Products Generating set, equipped with a VOLVO engine and LEROY SOMER alternator.

General characteristics



Electronic governor
Mechanically welded chassis with antivibration suspension
Main line circuit breaker
Radiator for wiring temperature of 48/50°C max with mechanical fan
Protective grille for fan and rotating parts
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
24 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation



Voltage (V) ESP Power (kWe/kVA) PRP Power (kWe/kVA) Back-up power (A) Dimensions
(L. x l. x h.)
Weight
480/277250.4/313250.4/313376
440/254250.4/313250.4/313410
220/127250.4/313250.4/313821
208/120250.4/313250.4/313868
240 TRI250.4/313250.4/313752
230 TRI250.4/313250.4/313785
600/347250.4/313250.4/313301
380/220250.4/313250.4/313475
Length : 2900 mm 2260 kg net
Width : 1300 mm 2650 kg gross
Height : 1590 mm




Hoods


Model dB(A)@1m dB(A)@7m Dimensions
(L. x l. x h.)
Weight Tank
M227 M227 84 84
Length : 4004mm
Width : 1380mm
Height : 2145mm
3190 kg net
3580 kg gross
390 L




Switch boxes available


Standard Control Panel TELYS
The highly versatile TELYS control unit is complex yet accessible, thanks to the particular attention paid to optimising its ergonomics and ease of use. With its large display screen, buttons and scroll wheel, it places the accent on simplicity and communication.

The TELYS offers the following functions:

Electrical measurements: voltmeter, frequency meter, ammeter.

Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage.

Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop, fuel level.

Ergonomics: wheel for navigating around the various menus.

Communication: remote control and operation software, USB connections, PC connection.

For more information on the product and its options, please refer to the sales documentation.

Optional control panel KERYS
The KERYS control unit has been designed to fulfil the specific requirements of professionals in terms of operating and monitoring generating sets. It therefore offers a wide range of functions.
This control unit is fitted as standard to all generating sets designed to be used for coupling and is offered as an option across the rest of our range.
The KERYS can be built into the central console, fitted directly on the generating set, or in a separate cabinet, to fulfil all the requirements for low and high output power plants.

>The KERYS offers the following functions:

Electrical measurements: voltmeter, frequency meter, ammeter.

Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage.

Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop.

Additional functions: coupling, website, diagnostic aid, assistance and maintenance, graphs and archiving, load impact management, 8 available installation configurations, certification in line with international standards.

For more information, please refer to the sales documentation.
Additional specifications :Website, Troubleshooting, Assistance and Maintenance, Plotting and logging, Load impact, 8 configurations available, Compliance with international standards...


Legal mentions - Map